The alarm log records every alarm with its date and time. TRAK Tech Support uses it to see what happened before a fault.

Saving the log needs no password. Copying it off the control needs the manufacturer password: TRAKmt2021.

If TRAK asks for the full diagnostic file instead, use Creating the DiDac Zipfile.

Other TRAKsi Tech Support guides: Software Version · Screenshot · Archive · Diagnostic File (DiDac) · Button-Press Log · ATC Magazine

  1. This works on every VMCsi and TCsi.
    • This works on every VMCsi and TCsi.

    • Press [Diagnostics] (triangle on the left) → [Alarm Log] → [Save Log].

    • This saves a time-stamped copy of the alarm log as a .txt file on the control.

  2. Opening the HMI data folder needs the manufacturer password. Enter TRAKmt2021 at [Setup] (wrench icon on the left) → [Set Password] (right column of softkeys). Go to [Setup] (wrench icon on the left) → [System data] (bottom row of softkeys).
    • Opening the HMI data folder needs the manufacturer password. Enter TRAKmt2021 at [Setup] (wrench icon on the left) → [Set Password] (right column of softkeys).

    • Go to [Setup] (wrench icon on the left) → [System data] (bottom row of softkeys).

    • In the folder list, open HMI data, then Logs, then Alarm Log.

    • Select the alarm log and press [Copy] (right column of softkeys).

    • At the top of the folder list, select the USB stick (USB Top or USB Bottom, right edge of the pendant) and press [Paste].

    • The alarm log saves to the USB stick as a .txt file.

    • Send it to TRAK with the other items on the TRAKsi Tech Support page.